Solar Safe Working Clearance Calculator
Safe Working Clearance Calculator
Look up minimum clearance distances per IE Rules 1956 Regulation 64 for any voltage level. Adjust any input and the result updates live.
Inputs
Updates liveResults
LiveMinimum clearance · 415 V
LV · standard PPE zone
IE Rule 64(1)(a) · IE Rules 1956
Workspace Width
mm corridor
Touch-Safe Dist.
mm
Glove Rating Required
Class 0 (1 kV maximum use)
Maintain ≥ 600 mm between any energised part and person. Working space (corridor) must be ≥ 1600 mm wide. Use Class 0 gloves or higher.
“IE Rules 1956, Regulation 64: 'No person shall work on any electrical installation unless effective measures have been taken to prevent the person from coming in contact with any live conductor.' Clearances are mandatory minimums; site-specific risk assessment may require more.”
About the Safe Working Clearance
Safe working clearance (SWC) defines the minimum distance between a person and a live electrical conductor or equipment to prevent electric shock or arc flash injury — essential for anyone working on or near energised solar, BESS, or substation equipment.
Last updated · How we build our calculators
How to calculate it
- 1Find the system voltage (phase to phase).
- 2Keep the minimum approach distance for that voltage from the CEA safety regulations (which replaced the IE Rules 1956) and your site's safety rules; this calculator's distance table is a guide and has not been checked against the regulations.
- 3Gloves: the lowest IEC 60903 class whose maximum use voltage covers the system voltage — Class 0 up to 1 kV, Class 1 to 7.5 kV, Class 2 to 17 kV, Class 3 to 26.5 kV, Class 4 to 36 kV. Above 36 kV no glove class applies: use hot-stick tools or de-energise.
- 4Issue a permit to work that names the isolation points and the safe boundary.
- 5For HV switchgear, add the arc-flash boundary and PPE from an arc-flash study.
Worked example
Work near a 33 kV panel: Class 4 gloves (36 kV maximum use); at 11 kV, Class 2 (17 kV); at 415 V, Class 0 (1 kV). At 66 kV no glove class applies — de-energise or use hot sticks. On a PV string's DC side up to 1,500 V, Class 0 gloves (1,500 V DC maximum use).
What you can calculate
- Glove class (IEC 60903)
- LT to HV
- Working space
- Pass/Fail
Standards & references
Frequently asked questions
Can solar panels be made safe for working on the roof?
Not completely in daylight — modules keep generating DC voltage while light falls on them. To work safely: isolate at the inverter DC isolator and the AJB to break the current path, cover the modules or work in low light where the task allows, use insulated tools and Class 0 gloves, and confirm with a calibrated DC meter before touching anything.
What PPE is required for solar electrical work in India?
For LV and PV DC work: Class 0 insulating gloves (1,000 V AC or 1,500 V DC maximum use, IEC 60903) with leather protectors, eye and face protection, and insulated tools (IEC 60900). For HV: only authorised persons, with gloves of the class for the voltage or hot sticks, and arc-rated clothing from an arc-flash study.
Ready to build your solar project?
Get free quotes from verified EPCs and installers across India.
You might also need
Pedestal Height
Calculate front and rear pedestal heights for target module tilt on flat rooftops
OpenModule Layout Planner
Plan tables, rows and string configuration for a rooftop array
OpenSetback from Parapet
Calculate minimum module setback from parapet walls to avoid shading
OpenBallast Weight
Calculate ballast required to resist IS 875 Part 3 wind uplift without penetrations
OpenWind Load (Rooftop)
Calculate uplift and lateral wind forces on rooftop PV modules per IS 875 Part 3
OpenAnchor Bolt Sizing
Check anchor bolt steel tension (IS 800) against factored wind uplift and count the bolts
Open