Solar Structure Deflection Calculator
Structure Deflection Calculator
Verify purlin / rafter deflection under dead + wind load against your deflection limit. Adjust any input and the result updates live.
Inputs
Updates liveyour design limit — IS 800 Table 6 and the module maker's mounting rules
Results
LivePASS · ample headroom
Actual Deflection
mm (δ)
Allowable (L/200)
mm limit
δ = 5wL⁴ / 384EI · E = 70,000 N/mm²
Safe — 60% headroom below the L/200 limit
“Mid-span deflection of a simply supported member under a uniform load: δ = 5wL⁴ ÷ 384EI (E: steel 200,000 MPa per IS 800, aluminium 70,000 MPa). The limit is your input: IS 800:2007 sets deflection limits by member and what it supports (cl. 5.6.1, Table 6), and module makers set limits for their mounting rails. Deflection only — check bending strength separately (IS 800 Section 8), with loads from IS 875.”
About the Structure Deflection
A deflection check confirms that mounting-structure members (purlins, rafters, rails) do not sag beyond the design limit under wind and dead load — excessive deflection stresses modules and clamps.
Last updated · How we build our calculators
Formula
δ = 5 × w × L⁴ ÷ (384 × E × I) · allowable = L ÷ n
- w
- Uniform load on the member (N/mm)
- L
- Span (mm)
- E
- Elastic modulus: steel 200,000 MPa (IS 800), aluminium 70,000 MPa
- I
- Second moment of area of the section (mm⁴)
- n
- Your deflection limit (span ÷ n), from IS 800 Table 6 and the module maker's mounting rules
How to calculate it
- 1Find the load per metre on the member from the dead load and the IS 875 wind load.
- 2Compute the mid-span deflection of the simply supported member.
- 3Compare it with span ÷ n; IS 800:2007 sets deflection limits by member and what it supports (cl. 5.6.1, Table 6), and module makers set limits for their rails.
- 4If it is over, choose a stiffer section or shorten the span.
- 5Check bending strength separately (IS 800 Section 8): a member can meet the deflection limit and still be overstressed.
Worked example
An aluminium purlin (I = 25 cm⁴) spanning 1.5 m under 800 N/m (the calculator's defaults): δ = 5 × 0.8 × 1,500⁴ ÷ (384 × 70,000 × 250,000) = 3.0 mm. At L/200 the allowable is 7.5 mm, so it uses 40 % of the limit.
What you can calculate
- δ = 5wL⁴/384EI
- Your L/n limit
- IS 800:2007
- Utilization ratio
Standards & references
Frequently asked questions
What is the allowable deflection for a solar structure?
It depends on the member and what it supports: IS 800:2007 Table 6 gives deflection limits by member type, and module makers state how much their mounting rails may deflect. Use the stricter of the two; this calculator takes the limit as span ÷ n, defaulting to L/200.
Ready to build your solar project?
Get free quotes from verified EPCs and installers across India.
You might also need
Pedestal Height
Calculate front and rear pedestal heights for target module tilt on flat rooftops
OpenModule Layout Planner
Plan tables, rows and string configuration for a rooftop array
OpenSetback from Parapet
Calculate minimum module setback from parapet walls to avoid shading
OpenBallast Weight
Calculate ballast required to resist IS 875 Part 3 wind uplift without penetrations
OpenWind Load (Rooftop)
Calculate uplift and lateral wind forces on rooftop PV modules per IS 875 Part 3
OpenAnchor Bolt Sizing
Check anchor bolt steel tension (IS 800) against factored wind uplift and count the bolts
Open